Voltage Drop Calculator
Calculate voltage drop in electrical circuits. Check NEC 3% and 5% compliance with wire size recommendations and power loss estimates.
Circuit Information
Use 8 AWG copper wire to achieve less than 3% voltage drop.
Detailed Results
NEC Voltage Drop Guidelines
| Rule | Max Drop | Application | Status |
|---|---|---|---|
| NEC 210.19(A)(1) | 3% | Branch circuits | ✗ Fail |
| NEC 215.2(A)(3) | 5% | Feeder + branch combined | ✗ Fail |
Wire Size Reference (Copper)
| AWG | Ampacity | Ω/1000ft | $/ft |
|---|---|---|---|
| 14 AWG | 15A | 2.525 | $0.20 |
| 12 AWG | 20A | 1.588 | $0.30 |
| 10 AWG | 30A | 0.999 | $0.50 |
| 8 AWG | 40A | 0.628 | $0.85 |
| 6 AWG | 55A | 0.395 | $1.30 |
| 4 AWG | 70A | 0.249 | $2.10 |
| 2 AWG | 95A | 0.156 | $3.30 |
| 1/0 AWG | 125A | 0.098 | $5.30 |
- Keep branch circuit voltage drop under 3% per NEC recommendation
- Total drop (feeder + branch) should not exceed 5%
- Motors are sensitive to voltage drop - size wire carefully
- Aluminum wire requires one size larger than copper for same ampacity
- Consider future load growth when sizing wire
Related Calculators
About This Calculator
Excessive voltage drop wastes energy, damages equipment, and can prevent motors from starting. Our comprehensive Voltage Drop Calculator determines if your wire size is adequate for a given circuit length, load, and voltage—helping electricians, contractors, and DIYers ensure both code compliance and optimal electrical system performance.
The National Electrical Code (NEC) recommends limiting voltage drop to 3% on branch circuits and 5% total from service entrance to final outlet. While these are recommendations rather than requirements, most inspectors and Authorities Having Jurisdiction (AHJ) enforce them. For a 120V circuit, 3% means no more than 3.6V drop; for 240V, no more than 7.2V.
In 2026, copper wire prices have increased significantly due to commodity markets, with 12 AWG Romex costing $0.45-0.90 per foot and larger conductors rising proportionally. Understanding voltage drop calculations helps you size wire correctly the first time—avoiding the costly mistake of undersized wire that fails inspection or the unnecessary expense of oversized conductors.
Trusted Sources
How to Use the Voltage Drop Calculator
- 1Enter the one-way wire length from panel to load (not round-trip distance).
- 2Enter the current (amperage) of the load or circuit breaker rating.
- 3Select the wire gauge (AWG) you plan to use or are evaluating.
- 4Choose the system voltage (120V, 240V single-phase, or 208V/480V three-phase).
- 5Toggle Advanced Mode for copper vs. aluminum selection and temperature derating.
- 6Review voltage drop in volts and percentage.
- 7Check NEC compliance status (green for ≤3%, yellow for 3-5%, red for >5%).
- 8If drop exceeds recommendations, increase wire size and recalculate.
- 9Use the wire size recommendation feature for automatic optimal sizing.
Formula
VD = (2 × K × I × L) ÷ CMVoltage drop (VD) equals 2 times the resistivity constant (K = 12.9 for copper, 21.2 for aluminum), times current (I in amps), times one-way length (L in feet), divided by circular mils (CM) of the wire. The factor of 2 accounts for round-trip current flow (hot and neutral). For three-phase, replace 2 with 1.732 (√3). Voltage drop percentage = (VD ÷ Source Voltage) × 100.
NEC Voltage Drop Requirements and Recommendations
The National Electrical Code provides voltage drop guidance in informational notes:
NEC Voltage Drop Recommendations:
| Application | Max Recommended | NEC Reference | Notes |
|---|---|---|---|
| Branch circuit | 3% | 210.19(A)(1) FPN | From panel to outlet |
| Feeder | 3% | 215.2(A)(3) FPN | From service to sub-panel |
| Total circuit | 5% | 215.2(A)(3) FPN | Service to final outlet |
| Sensitive equipment | 2% | Optional | Computers, medical equipment |
Important Distinction: These are Fine Print Notes (FPN), meaning recommendations for efficiency, not mandatory requirements. However:
- Most AHJs (Authorities Having Jurisdiction) enforce them
- Many specifications require compliance
- Exceeding 5% may cause equipment problems
- Insurance and liability considerations apply
What Voltage Drop Percentages Mean:
| Voltage Drop | Status | Effect |
|---|---|---|
| ≤3% | Excellent | Meets NEC recommendation for branch circuits |
| 3-5% | Acceptable | Meets NEC total recommendation but at limits |
| 5-8% | Marginal | May cause problems, some equipment affected |
| 8-10% | Poor | Motors may not start, lights noticeably dim |
| >10% | Unacceptable | Equipment damage likely, fire hazard |
Actual Voltage at Load (120V system):
| Drop % | Voltage at Load | Status |
|---|---|---|
| 3% | 116.4V | Recommended |
| 5% | 114V | Maximum |
| 10% | 108V | Problematic |
Wire Gauge Reference and Ampacity
American Wire Gauge (AWG) uses a counterintuitive system: smaller numbers = thicker wire = lower resistance = less voltage drop.
Copper Wire Properties (75°C Rating, THWN/THHN):
| AWG | Diameter (mils) | Circular Mils | Ω/1000ft @ 75°C | Ampacity |
|---|---|---|---|---|
| 14 | 64.1 | 4,110 | 3.14 | 15A |
| 12 | 80.8 | 6,530 | 1.98 | 20A |
| 10 | 101.9 | 10,380 | 1.24 | 30A |
| 8 | 128.5 | 16,510 | 0.778 | 40A |
| 6 | 162.0 | 26,240 | 0.491 | 55A |
| 4 | 204.3 | 41,740 | 0.308 | 70A |
| 3 | 229.4 | 52,620 | 0.245 | 85A |
| 2 | 257.6 | 66,360 | 0.194 | 95A |
| 1 | 289.3 | 83,690 | 0.154 | 110A |
| 1/0 | 324.9 | 105,600 | 0.122 | 125A |
| 2/0 | 364.8 | 133,100 | 0.0967 | 145A |
| 3/0 | 409.6 | 167,800 | 0.0766 | 165A |
| 4/0 | 460.0 | 211,600 | 0.0608 | 195A |
Aluminum Wire (61% Conductivity of Copper):
| AWG | Ω/1000ft | Ampacity | Copper Equivalent |
|---|---|---|---|
| 12 | 3.25 | - | Not recommended |
| 10 | 2.04 | - | Not recommended |
| 8 | 1.28 | 30A | 10 AWG copper |
| 6 | 0.808 | 40A | 8 AWG copper |
| 4 | 0.508 | 55A | 6 AWG copper |
| 2 | 0.319 | 75A | 4 AWG copper |
| 1/0 | 0.201 | 100A | 2 AWG copper |
| 2/0 | 0.159 | 115A | 1 AWG copper |
| 4/0 | 0.100 | 150A | 1/0 AWG copper |
Key Rule: For aluminum, use wire two sizes larger than copper for equivalent performance.
2026 Wire Pricing and Cost Considerations
Copper prices have reached five-year highs, significantly impacting electrical wire costs:
2026 Romex (NM-B) Pricing:
| Size | Price per Foot | 250ft Roll | Typical Use |
|---|---|---|---|
| 14/2 NM-B | $0.35-0.55 | $90-140 | 15A lighting circuits |
| 12/2 NM-B | $0.45-0.70 | $115-175 | 20A general circuits |
| 10/2 NM-B | $0.75-1.10 | $190-275 | 30A dryer, A/C |
| 10/3 NM-B | $1.10-1.50 | $275-375 | 30A dryer with neutral |
| 8/3 NM-B | $2.00-2.75 | $500-690 | 40A range |
| 6/3 NM-B | $3.25-4.25 | $815-1,060 | 50A range, sub-panel |
THHN/THWN (Conduit Wire) Pricing:
| Size | Copper/ft | Aluminum/ft | Typical Use |
|---|---|---|---|
| 12 AWG | $0.25-0.40 | - | Branch circuits |
| 10 AWG | $0.40-0.60 | - | 30A circuits |
| 8 AWG | $0.65-0.95 | $0.35-0.50 | Sub-feeders |
| 6 AWG | $1.00-1.50 | $0.50-0.75 | 50-60A feeders |
| 4 AWG | $1.60-2.30 | $0.80-1.15 | 70A feeders |
| 2 AWG | $2.50-3.50 | $1.25-1.75 | 100A feeders |
| 1/0 AWG | $4.00-5.50 | $2.00-2.75 | 125A service |
| 4/0 AWG | $8.00-11.00 | $4.00-5.50 | 200A service |
Cost of Upsizing for Voltage Drop:
| Upgrade | Additional Cost/100ft | When Worth It |
|---|---|---|
| 12 → 10 AWG | $30-50 | Runs >55 ft |
| 10 → 8 AWG | $50-85 | Runs >88 ft |
| 8 → 6 AWG | $60-100 | Runs >140 ft |
| 6 → 4 AWG | $90-130 | Runs >220 ft |
Key Insight: The cost of upsizing wire is often minimal compared to reinstallation costs if undersized wire fails inspection.
Maximum Wire Run Distances
These tables show maximum one-way distances for 3% voltage drop at full rated load:
120V Single-Phase Circuits:
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|
| 10A | 45 ft | 70 ft | 115 ft | 180 ft | 290 ft |
| 15A | 30 ft | 50 ft | 75 ft | 120 ft | 190 ft |
| 20A | - | 35 ft | 55 ft | 90 ft | 145 ft |
| 30A | - | - | 40 ft | 60 ft | 95 ft |
| 40A | - | - | - | 45 ft | 70 ft |
240V Single-Phase Circuits:
| Load | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|---|---|
| 15A | 60 ft | 95 ft | 155 ft | 245 ft | 390 ft | 620 ft |
| 20A | 45 ft | 70 ft | 115 ft | 185 ft | 290 ft | 465 ft |
| 30A | - | 50 ft | 75 ft | 120 ft | 195 ft | 310 ft |
| 40A | - | - | 55 ft | 90 ft | 145 ft | 230 ft |
| 50A | - | - | - | 70 ft | 115 ft | 185 ft |
208V/240V Three-Phase Circuits:
| Load | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
|---|---|---|---|---|---|
| 30A | 90 ft | 145 ft | 230 ft | 370 ft | 580 ft |
| 50A | 55 ft | 85 ft | 140 ft | 220 ft | 350 ft |
| 75A | - | 60 ft | 95 ft | 150 ft | 235 ft |
| 100A | - | - | 70 ft | 110 ft | 175 ft |
Note: These distances assume copper wire at 75°C. Reduce by 20-40% for aluminum.
Common Long-Run Applications
Certain installations commonly require voltage drop calculations:
Outbuildings (Garage, Shop, Barn):
| Distance | 100A Service | Recommended Wire |
|---|---|---|
| 50 ft | 3% drop | 2 AWG copper or 1/0 aluminum |
| 100 ft | 3% drop | 1/0 AWG copper or 3/0 aluminum |
| 150 ft | 3% drop | 2/0 AWG copper or 4/0 aluminum |
| 200 ft | 3% drop | 3/0 AWG copper or 250 MCM aluminum |
Well Pumps and Water Systems:
| HP | Running Amps (240V) | Max Distance @ 10 AWG | @ 8 AWG |
|---|---|---|---|
| 1/2 HP | 5A | 230 ft | 365 ft |
| 3/4 HP | 7A | 165 ft | 260 ft |
| 1 HP | 9A | 125 ft | 200 ft |
| 1.5 HP | 12A | 95 ft | 150 ft |
| 2 HP | 15A | 75 ft | 120 ft |
EV Charger Installations (240V):
| Level 2 Rating | Current | Max Distance @ 6 AWG | @ 4 AWG |
|---|---|---|---|
| 7.2 kW | 30A | 95 ft | 155 ft |
| 9.6 kW | 40A | 70 ft | 115 ft |
| 12 kW | 50A | 55 ft | 90 ft |
Pool/Spa Equipment:
| Equipment | Typical Load | Considerations |
|---|---|---|
| Pool pump | 10-20A @ 240V | Often 100+ ft from panel |
| Spa heater | 30-50A @ 240V | High continuous load |
| Pool heater | 50-100A @ 240V | Size for nameplate + 25% |
Solutions for Long Runs:
- Upsize wire - Most common, adds material cost
- Install sub-panel - Reduces long circuit runs
- Run higher voltage - 240V drops half as much as 120V
- Parallel conductors - For very large loads
Effects of Voltage Drop on Equipment
Voltage drop affects different equipment types in specific ways:
Motor Loads (Most Sensitive):
| Voltage Drop | Effect on Motors |
|---|---|
| 5% | Starting torque reduced 10%, may struggle under load |
| 10% | Starting torque reduced 19%, may not start |
| 15% | Starting torque reduced 28%, definite no-start |
Motor current increases as voltage drops, potentially:
- Tripping overload protection
- Overheating windings
- Reducing motor lifespan by 50%+
- Causing nuisance tripping of breakers
Lighting Loads:
| Type | 5% Drop | 10% Drop |
|---|---|---|
| Incandescent | 16% dimmer, 50% shorter life | 30% dimmer, 75% shorter life |
| LED | Minor dimming | Possible flickering, driver stress |
| Fluorescent | May not start reliably | Frequent starting failures |
| HID | Color shift, may not restrike | Starting failures |
Heating Elements (Resistive Loads): Power output follows voltage squared:
| Voltage Drop | Power Reduction |
|---|---|
| 3% | 6% reduction |
| 5% | 10% reduction |
| 10% | 19% reduction |
| 15% | 28% reduction |
A 5,000W heater at 10% voltage drop delivers only 4,050W.
Electronic Equipment:
| Equipment | Minimum Voltage | Effect of Low Voltage |
|---|---|---|
| Computers | 104-108V | Random crashes, data loss |
| Refrigerators | 105-110V | Compressor damage |
| Sensitive electronics | 108-114V | Malfunction, damage |
| Battery chargers | Varies | Incomplete charging |
Copper vs. Aluminum Wire
Choosing between copper and aluminum involves cost, performance, and application considerations:
Material Properties:
| Property | Copper | Aluminum |
|---|---|---|
| Conductivity | 100% (reference) | 61% |
| Weight | Heavier | 70% lighter |
| Ω/1000ft (12 AWG) | 1.98 | 3.25 |
| Expansion rate | 0.0000094/°F | 0.0000128/°F |
| Cost (relative) | 100% | 40-50% |
When to Use Aluminum:
- Service entrance conductors (4/0, 3/0, 2/0)
- Sub-panel feeders (4 AWG and larger)
- Long runs where weight matters
- Budget-constrained large feeders
- Underground service laterals
When to Use Copper:
- Branch circuits (always)
- Connections to standard outlets/switches
- Where space is limited
- Exposed or flexible applications
- Motor connections (less expansion)
Aluminum Installation Requirements:
- Use AL/CU rated devices and breakers
- Apply anti-oxidant compound
- Torque connections to specification
- Allow for thermal expansion
- Use compression connectors, not set screws
- Size two gauges larger than copper equivalent
2026 Cost Comparison (200A Service, 100ft):
| Material | Wire Size | Cost | Installation |
|---|---|---|---|
| Copper | 3/0 AWG | $1,100-1,500 | Standard |
| Aluminum | 4/0 AWG | $450-650 | Requires AL-rated equipment |
| Savings | - | $600-900 | Worth it for long feeders |
Three-Phase Voltage Drop
Three-phase systems have different voltage drop characteristics:
Three-Phase Formula:
VD = (√3 × K × I × L) ÷ CM
= (1.732 × K × I × L) ÷ CM
Why √3? In three-phase systems, current flows through only one wire at a time (not round-trip like single-phase), but the phase relationship creates a 1.732 multiplier.
Common Three-Phase Voltages:
| Voltage | Application | Phase-to-Neutral |
|---|---|---|
| 208V | Commercial, small industrial | 120V |
| 240V | Industrial delta | N/A |
| 277V | Commercial lighting | N/A |
| 480V | Industrial motors | 277V |
| 600V | Heavy industrial | 347V |
Three-Phase Advantages:
- More efficient power transmission
- Smaller wire for same power
- Less voltage drop per kW delivered
- Motors run smoother
208V vs. 240V Three-Phase:
| Factor | 208V Wye | 240V Delta |
|---|---|---|
| Source | Utility transformer | Delta transformer |
| Neutral | Available (120V) | Not typically available |
| Motor compatibility | 208V rated | 230V rated |
| Voltage drop | Slightly higher | Slightly lower |
Example Calculation (480V, 100A, 200ft, 1/0 copper):
VD = (1.732 × 12.9 × 100 × 200) ÷ 105,600
VD = 446,760 ÷ 105,600
VD = 4.23V (0.88%)
Three-phase at 480V experiences much less percentage drop than single-phase at 120V.
Temperature and Derating Factors
Wire resistance increases with temperature, affecting voltage drop:
Temperature Correction Factors:
| Ambient Temp | 60°C Wire | 75°C Wire | 90°C Wire |
|---|---|---|---|
| 70°F (21°C) | 1.08 | 1.04 | 1.00 |
| 86°F (30°C) | 1.00 | 1.00 | 1.00 |
| 104°F (40°C) | 0.82 | 0.88 | 0.91 |
| 122°F (50°C) | 0.58 | 0.75 | 0.82 |
| 140°F (60°C) | - | 0.58 | 0.71 |
Resistance Change with Temperature: Copper resistance increases approximately 0.4% per °C above 20°C.
Bundled Conductors (NEC 310.15(B)(3)):
| Conductors | Adjustment Factor |
|---|---|
| 4-6 | 0.80 (80%) |
| 7-9 | 0.70 (70%) |
| 10-20 | 0.50 (50%) |
| 21-30 | 0.45 (45%) |
Conduit Fill Derating: More wires = more heat = higher resistance = more voltage drop.
Ambient Temperature Locations:
| Location | Typical Temp | Consideration |
|---|---|---|
| Indoor conditioned | 77°F | Standard |
| Attic | 120-150°F | Significant derating |
| Roof conduit | 130-160°F | Severe derating |
| Underground | 68-77°F | Minimal adjustment |
| Direct sunlight | +30°F | Add to ambient |
Practical Impact: A circuit calculated at 2.8% voltage drop at 75°F may exceed 3% at 120°F attic temperatures.
Pro Tips
- 💡When in doubt, go up one wire size—the extra cost is typically 15-30% and avoids failed inspections.
- 💡For motors, always size wire for 125% of nameplate full-load amps per NEC 430.22.
- 💡Use 240V instead of 120V for long runs—voltage drop percentage is cut in half.
- 💡Calculate at the full expected load, not the breaker rating, for more accurate results.
- 💡Consider future load growth—upsizing now is cheaper than rewiring later.
- 💡For aluminum wire, always use anti-oxidant compound and AL-rated devices.
- 💡Temperature derating in hot locations (attics, rooftops) can push a marginal circuit over limits.
- 💡Sub-panels are often more cost-effective than oversized wire for distant loads.
- 💡Document your voltage drop calculations for permit inspections.
- 💡For EV chargers, size for full rated capacity even if you start with lower charging rates.
- 💡Conduit fill derating affects both ampacity AND increases resistance due to heat.
- 💡Three-phase 208V is NOT the same as single-phase 240V—motors must be rated correctly.
Frequently Asked Questions
No, NEC 3% and 5% limits are recommendations in Fine Print Notes, not enforceable requirements. However, most local Authorities Having Jurisdiction (AHJ) and inspectors enforce them. Additionally, exceeding 5% can cause equipment problems and liability issues. Always check with your local building department.

